Dimensioni Ø circa 5/10 mm
numero di articolo 030050
L'impermeabilizzazione dei giunti delle costruzioni in calcestruzzo pone requisiti elevati alla tecnologia di sigillatura.
Il tubo di iniezione MASTERTUBE garantisce una sigillatura affidabile e duratura dei giunti orizzontali e verticali delle costruzioni in calcestruzzo contro l'acqua in pressione e non. Aggiungi all'elenco degli avvisiLe informazioni più importanti in un colpo d'occhio
Camera d'aria in PVC
Guaina in tessuto monofilamento
ca. 10 mm
circa 5 mm
Luminoso, con funzione di valvola
depending on injection agent,
approx. + 6°C to +40°C
Certificato di collaudo dell'autorità edilizia generale (AbP)
MFPA Lipsia
Nr.: P-SAC 02 / 5.1 / 21 - 266-1 (resina PU)
Nr.: P-SAC 02 / 5.1 / 21 - 266-2 (acrilato)
Fino a max. 2 bar ( 20 m di colonna d'acqua )
Ja
Utilizzare la classe A per le classi di carico 1 e 2 secondo le linee guida WU
.1 Rolle in 100 m
.
The product is supplied on a 100 m reel.
Bind the hose with filament tape and use a suitably sharp tool to cut the hose to the required length.
Injection circuits must not exceed 8 m in length.
After the hose has been cut to length, screw the respective connecting pieces fully into the hose (as far as they will go) - the image shows our fastening packers.
Place the hose centrally in the construction joint, within the reinforcement.
The surface of the construction joint must be clean, level and free of burrs, defects and loose particles of dirt.
The hose can be fastened in place with metal clips for nailing (manual or nail gun).
The distance between the fastening clips must not exceed 15 cm.
Alternatively, the hose can be fastened in place with plastic clips, either set in the fresh concrete or subsequently hammered into an 8 mm drill hole.
The distance between the fastening clips must not exceed 15 cm.
The hose must be in continuous contact with the concrete and must not be allowed to float.
Fixing on joints with category "rough"
On construction joints with a rough surface, fastening with a fastening grid is necessary to ensure full-surface support on the construction joint. The fixing grid is placed over the hose and fixed alternately (to the left and right of the hose) with nail plugs every 15 cm maximum.
Successive injection hose sections must overlap by at least 20 cm in order to ensure continuous injection of the joint.
All changes in direction must be implemented with a sufficiently wide bending radius in order not to damage the hose/restrict the overall injection flow.
The minimum radius is 5 cm.
The injection and ventilation ends can be kept in storage boxes, or alternatively the hose end can be attached to the formwork itself using fastening packers. The storage boxes or fastening packers must be arranged so they are easily accessible in the event of subsequent injection procedures (take high floor structures into consideration).
Once the concrete has cured, the resin can be injected via the fastening packers or the injection end pieces.
Status: 23.03.2022
HOSE CONNECTOR / VENTILATION HOSE / SEALING PLUG / STORAGE BOX in in-situ concrete
Scarica il DWG Scaricare PDFAccessori
accessori adatti
Il packer di fissaggio MASTERTEC consente di fissare il tubo di iniezione direttamente alla cassaforma. Il packer di fissaggio co...
Clip di fissaggio per l'installazione a prova di galleggiamento di tubi di iniezione su superfici in calcestruzzo ...
Resina poliuretanica per iniezione di tubi e fessure ...
Prodotti simili
Potete trovare prodotti simili qui.
L'impermeabilizzazione dei giunti delle costruzioni in calcestruzzo pone requisiti elevati alla tecnologia di sigillatura.Il ...
Contattateci
Siamo lieti di rispondere alle vostre domande